Industrial Cyber
Inside OT’s Fundamentals Gap: A PLC Fault, an AI Exploit, and Leaked Identities
On October 27, Google published its final incident report on the London power failure that took its europe-west2-b zone offline a week earlier, disrupting Revolut, Lloyds Banking Group, HSBC, and the video links used for remote court hearings in England and Wales. According to Google, the undervoltage sensing inputs on the programmable logic controllers that start the facility’s generator plant were wired on the line side of a utility breaker that had been isolated for repairs.