CVE-2025-41669: AXC F 1152 0.0.0 to before 2026.0.3; +13 more affected products
CVE-2025-41669. CVSS 3.1 base score 8.8 (HIGH, Vendor/CNA). EPSS 0.00218 (percentile 0.11342), scored 13-Oct-2026.
Affected technology
AXC F 1152 · 0.0.0 to before 2026.0.3
Phoenix Contact
AXC F 1252 · 0.0.0 to before 2026.0.3
Phoenix Contact
AXC F 2000 EA · 0.0.0 to before 2026.0.3
Phoenix Contact
AXC F 2152 · 0.0.0 to before 2026.0.3
Phoenix Contact
AXC F 3152 · 0.0.0 to before 2026.0.3
Phoenix Contact
BPC 9102S · 0.0.0 to before 2026.0.3
Phoenix Contact
EPC 1522 · 0.0.0 to before 2026.0.3
Phoenix Contact
RFC 4072R · 0.0.0 to before 2026.0.3
Phoenix Contact
RFC 4072S · 0.0.0 to before 2026.0.3
Phoenix Contact
VL3 UPC 2440 EDGE · 0.0.0 to before 2026.0.3
Phoenix Contact
VPLCNEXT CONTROL 1000 · 0.0.0 to before 2026.0.3
Phoenix Contact
VPLCNEXT CONTROL 2000 · 0.0.0 to before 2026.0.3
Phoenix Contact
VPLCNEXT CONTROL 3000 · 0.0.0 to before 2026.0.3
Phoenix Contact
VPLCNEXT CONTROL 500 · 0.0.0 to before 2026.0.3
Phoenix Contact
Component: Not specified by the source
Attack conditions (Vendor/CNA, CVSS 4.0): Network (remote) · Low privileges required · No user interaction required
What an attacker can do
A remote low privileged Engineer user can install additional APPs on the device downloaded from the PLCnext Store without implementing any data verification mechanism, leading to the capability for an Engineer user to reach arbitrary code execution with root privileges on the PLC device. Vendor/CNA’s CVSS 4.0 assessment (base score 8.7/10) rates confidentiality, integrity and availability impact as high.
- CWE
- CWE-347
- CCR priority
- 35.3 /100 (P4)
- CVSS 3.1
- 8.8 /10 · CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H · Vendor/CNA
- EPSS